6 examples for self-tuning attempts 16, Cancelation causes 16, Operation – West Control Solutions KS 42-1 User Manual

Page 16

Advertising
background image

3.5.5 Acknowledgement procedures in case of unsuccessful self-tuning

1. Press keys

Ù and È simultaneously:

The controller continues controlling using the old parameters in automatic
mode. The Err LED continues blinking, until the self-tuning error was
acknowledged in the error list.

2. Press key

Ò (if configured):

The controller goes to manual mode. The Err LED continues blinking,
until the self-tuning error was acknowleged in the error list.

3. Press key

Ù :

Display of error list at extended operating level. After acknowledgement
of the error message, the controller continues control in automatic mode using
the old parameters.

Cancellation causes:
r page 13: "Error status self-tuning heating ( ADA.H) and cooling ( ADA.C)"

3.5.6 Examples for self-tuning attempts

(controller inverse, heating or heating/cooling)

Start: heating power switched on
Heating power Y is switched off (1).
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning
attempt is finished and the new para-
meter are used for controlling to
set-point W.

Start: heating power switched off
The controller waits 1,5 minutes (1).
Heating power Y is switched on (2).
At the reversal point, the self-tuning
attempt is finished and control to the
set-point is using the new parameters.

Operation

Self-tuning

16

Operating KS4x-1

t

2

100%

Y

0%

X

W

Start r

1

3

t reversal point

blinks

t

100%

Y

0%

X

W

start r

1

2

t reversal point

blinks

Advertising