Electrical connections 11, 1 connecting diagram 11, 2 terminal connections 11 – West Control Solutions SG 45 User Manual

Page 11: Inp1 11, Connecting diagram 11, 13, 4 electrical connections, Connecting diagram, Terminal connections

Advertising
background image

.

4

Electrical connections

4.1

Connecting diagram

4.2

Terminal connections

a

Faulty connection might cause destruction of the instrument !

1 Connecting the supply voltage

Dependent on order

90 … 260 V AC

terminals: 15,16

24 V AC / DC

terminals: 15,16

For further information, see section

"Technical data"

g

Instruments with optional system interface:
Energization is via the bus connector of field bus coupler or power supply module. Terminals 15, 16 must
not be used.

2 Connecting input INP1

Input for strain gauge (in 4 and 6-wire connection) or for melt pressure sensors (with/without calibration shunt).
a

Excitation voltage for bridge (EXITATION )

terminals: 1, 4

b

Excitation voltage measuring signal (Sense)

terminals: 2, 3

c

Bridge signal (input)

terminals: 5, 6

Electrical connections

SG 45

Connecting diagram

11

Data A

Data A

Data B

Data B

OUT3

PWR

OUT1

OUT2

di1

RGND

RGND

RS 485

1

INP1

2

3

4

5

6

a

c

b

d

e

11 12 13 14

11 12 13 14

15 16 17 18

15 16 17 18

1 2 3 4

1 2 3 4

top

14

13

12

16

15

11

17 18

L

N

~90-260V

~24V

V

16

15

17 18

System

8

7

6

3

2

1

5

3

4

INP

+

-

EX +

EX -

+ Sense -

R-CAL