6.11

Limit value processing

Max. three limit values can be configured for the outputs. Generally, each one of outputs

Out.1... Out.2 can be

used for limit value or alarm signalling.

Several signals allocated to an output are linked by a logic OR function.

6.11.1

Input value monitoring

g

The signal to be monitored can be selected separately for each alarm in the configuration. The following
signals are available:

Process value (display value)

Measured value INP

Zero adjustment

Each of the 3 limit values

Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off

individually (parameter = “

OFF”). The hysteresis HYS.x of each limit value is adjustable.

Input value monitoring is as shown below:

Display range

Limit value 1

Outputs

Display range

Limit value 1

Outputs

Display range

Limit value 1

Outputs

Normally open:

(

ConF / Out.x / O.Act = 0 )

(as shown in the example)

Normally closed:

(

ConF / Out.x / O.Act = 1 )

(inverted output relay action)

Functions

UNIFLEX SG 45

Limit value processing

29

H.1

LED rot / red

HYS.1

-1999

9999

H.1

operating principle with absolute alarm (Ex. Lim.1)

L.1 = OFF

L.1

HYS.1

-1999

9999

LED rot / red

L.1

H.1 = OFF

L.1

LED

LED

HYS.1

HYS.1

H.1

-1999

9999

rot / red

rot / red

L.1

H.1