6.13

Maintenance manager / error list

In case of one or several errors, the error list is always displayed at the beginning of
the extended operating level .

A current input in the error list (alarm or error) is always indicated by display of letter E .

For display of the error list, press key ô once.

E- display element Description

Possible remedial action

blinks

Alarm due to existing error

- Determine the error type in the error list via the error number
- remove error

on

Error removed, Alarm not ac-
knowledged

- acknowledge alarm in the error list by pressing the È - or
the Ì -key
- the alarm entry is deleted by doing so

off

no error, all alarm entrys deleted

Error list:

Name

Description

Cause

Possible remedial action

E.1

Internal error, cannot be
corrected

E.g. defective EEPROM

Contact PMA service
Return device to manufacturer

E.2

Internal error, resettable

E.g. EMC trouble

Keep measuring and supply cables separate.
Protect contactors by means of RC snubber cir-
cuits

E.3

Configuration error, reset-
table

Missing or faulty configura-
tion

Check interdependencies for configurations and
parameters

E.4

Hardware error

Code number and hardware
not identical

Contact PMA service

FbF.1 INP*) sensor break

Defective sensor

Replace INP sensor

Wiring error

Check INP connection

Overshoot

Change the measuring range

POL.1 INP*) polarity error

Wiring error

Change INP polarity

Lim.1

Lim.2

Lim.3

Latched limit value alarm
1/2/3

Adjusted limit value 1/2/3
exceeded

Check process

Inf.1 Time limit value message

Preset number of operating
hours reached

Application-specific

Inf.2 Switching cycle messa-

ge(digital outputs)

Preset number of switching
cycles reached

Application-specific

*) “

FAIL” is shown on the process value display.

Functions

35

Maintenance manager / error list

SG 45

1 2 F

E

450.3

ыC

дььд

Advertising