background image

V

Installation, Operation

& Maintenance Manual

ENGLISH

te

XDS

Series

Surge Protective Device (SPD)

Bonding and Grounding Hazard

Verify that the neutral conductor in the service

entrance equipment is bonded to ground in

accordance with the National Electric Code

(NEC

®

) and all applicable codes.

Verify that the neutral terminal (XO) on the

secondary side of distribution transformers are

grounded to the system ground in accordance with

the NEC

®

and all applicable codes.

During installation into an electrical system the

SPD must not be energized until the electrical

system is completely installed, inspected and

tested. All conductors must be connected and

functional including the neutral (if required). The

voltage rating of the SPD and system must be

verified before energizing the SPD.

Failure to follow these guidelines can lead to

abnormally high voltages at the SPD. This may

cause the SPD to fail. The warranty is voided if the

SPD is incorrectly installed and/or if the neutral

conductor in the service entrance equipment or

downstream of separately derived systems is not

bonded to ground in accordance with the NEC

®

.

Do Not Hi-Pot Test SPDs

Any factory or on-site testing of power distribution

equipment that exceeds normal operating voltage

such as high-potential insulation testing, or any

other tests where the suppression components

will be subjected to higher voltage than their

rated Maximum Continuous Operating Voltage

(MCOV) must be conducted with the SPD

disconnected from the power source. For 4-wire

systems, the neutral connection at the SPD must

also be disconnected prior to performing high-

potential testing and then reconnected after test

completion.

Failure to disconnect SPD and associated

components during elevated voltage testing will

damage the SPD and will void the warranty.

Safety First – Hazardous Voltage & Shock Hazard

WARNING – IMPORTANT – PLEASE READ – WARNING

• Only qualified licensed electricians should install or service SPDs

• Hazardous voltages exist within SPDs

• SPDs should never be installed or serviced when energized

• Use appropriate safety precautions including personal protection equipment

• Failure to follow these instructions can result in death, serious injury and/or equipment damage

• This manual shall be read in its entirety prior to installing

INSTALLATION INSTRUCTIONS ON PAGE 6

Advanced Protection Technologies

14550 58th Street North, Clearwater, Florida 33760

(800) 237-4567 | (727) 535-6339 | Fax (727) 539-8955

www.aptsurge.com | [email protected]

UL is a registered trademark of Underwriters Laboratories, NEC

®

and National Electrical Code are

registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,

C62.45-2002, C62.72-2007 are registered trademarks of IEEE.

11.4.13.lh #8170