Figure 4 conduit installation, Figure 5 typical panel installation – Advanced Protection XDS User Manual

Page 6

Advertising
background image

INSTALLATION

Common Problems to Avoid:

• Confirm System voltage to SPD voltage (120V SPD will fail instantly on 240V, 277V, etc.).

• Locate SPD close so leads are short & straight as possible (or will seriously hurt performance).

• Make sure N-G or XO bonding meets NEC

®

(or will prematurely fail SPD).

• Energize SPD AFTER system is stabilized & checked (inadvertent system problem may fail SPD).

• SPDs are regulated by NEC

®

Article 285 and UL 1449.

• Never Hi-Pot test any SPD (will prematurely fail SPD).

• Do not install XDS through bottom of a NEMA 3R panel. (Dripping water will prematurely fail the SPD).

Pre-Plan your installation. You will need to accomplish the following:

• Meet all National and Local codes (NEC

®

Article 285 addresses SPDs).

• Mount SPD as close to panel or equipment as possible to keep leads short.

• Ensure leads are as short and straight as possible, including neutral and ground. Consider a

breaker position that is closest to the SPD and the panel’s neutral & ground.

• Suggested breaker and conductor size is 50A-30A with 8 AWG.

• Make sure system is grounded per NEC

®

and clear of faults before energizing SPD.

1. Use a voltmeter to check all voltages to ensure correct SPD.

2. If unit has Flush Mount option refer to Flush Mount Installation Instructions following.

3. If SPD has Dry Contact pre-plan its installation.

4. Remove power for panel. Confirm panel is deenergized.

5. Identify breaker location and SPD location.

6. Remove an appropriately sized knockout from panel.

7. Mount SPD, use appropriate weatherproofing equipment as needed.

8. Connect conductors as appropriate – short and straight as possible (Note that Hi-Legs are Phase B).

9. Label or mark conductors as appropriate (neutral: white, ground: green, energized: black, hi-leg: orange).

10. Make sure system is bonded per NEC

®

and is clear of hazards or faults before energizing

(N-G bonding not per NEC

®

will fail SPDs: #1 cause of SPD failures).

11. Energize and confirm proper operation of indicators and/or options.

A sealing O-ring is provided. SPD can be chase-nipple mounted (nut is provided).

Note that any conduits must be installed correctly.

Figure 4

CONDUIT INSTALLATION

CORRECT

INSTALLATION

Threaded 6

Full Turns

INCORRECT INSTALLATIONS

OVERTIGHTENED

Stresses box,

ONLY

6 full turns

required

POOR

ENGAGEMENT

Conduit needs

to be threaded

in farther

Figure 5

TYPICAL PANEL

INSTALLATION

A

B

C

G

N

BREAKER

• Use closest

breaker to SPD

• Locate SPD

close to intended

breaker

• Keep Leads Short

as Possible

• Avoid Sharp

Bends

Rotate XD such

that LED indicator is

most visible

Outdoor installation requires appropriate weather

sealing at nipple (o-ring, sealing conduit, etc.)

To Protected Loads

6

Advertising