Advanced Protection XDS User Manual

Page 4

Advertising
background image

Article 285. As a generalization, it is more practical

to install on load side of main overcurrent device

for maintenance reasons.

When connected on load side of main disconnect,

we suggest connecting via a 50-30A circuit

breaker. The circuit breaker is the intended

disconnect switch and provides short circuit

protection to the connecting conductors. The XD

Series has internal overload protection elements

within the product. A breaker or disconnect is not

required for the SPDs overcurrent protection. XD

SPDs have demonstrated 200kA Short Circuit

Current Ratings (SCCR). 120V and 120/240V

XDs have demonstrated 100kA SCCRs. Confer

to label on unit.

Terminals

Terminals will accept 14 - 8 AWG conductor and

are provided for line (phase), neutral (if used),

and equipment safety ground connections.

8 AWG is the minimum recommended wire

size because UL testing and evaluation was

performed using 8 AWG.

Wire Size and Installation Torque

This is a parallel-connected SPD; it is not

series-connected. The size of the SPD wiring is

independent of the ampere rating of the protected

circuit. Recommended wire is 8 AWG for

phase, neutral and ground connections. Torque

connections to 18 inch-pounds. Conductor length

should be as short as possible.

If other wire sizes are used, we recommend that

all conductors be the same gauge. Note that

larger conductor might appear to be beneficial;

however, it tends to have the same inductance

as smaller conductor and is more difficult to work

with. Terminals accept 14 - 8 AWG conductor with

8 AWG being preferred. Coordinate conductor size

and overcurrent protection per applicable codes.

System Grounding

An equipment grounding conductor must be used

on all electrical circuits connected to the SPD.

For the best performance, use a single point

ground system where the service entrance

grounding electrode system is connected to

and bonded to all other available electrodes,

building steel, metal water pipes, driven rods, etc.

(for reference see: IEEE Std 142-2007).

For sensitive electronics and computer systems,

we recommend that the ground impedance

measurement be as low as possible. When

metallic raceway is used as an additional

grounding conductor, an insulated grounding

conductor should be run inside the raceway and

sized per the NEC

®

. Adequate electrical continuity

must be maintained at all raceway connections.

Do not use isolating bushings to interrupt a

metallic raceway run.

A separate isolated ground for the SPD is NOT

recommended. Proper equipment connections

to grounding system and ground grid continuity

should be verified via inspections and testing

on a regular basis as part of a comprehensive

electrical maintenance program.

On 4-Wire Power Systems, neutral to ground

bonding (Main Bonding Jumper) must be installed

per the NEC

®

. Failure to do so WILL damage SPDs.

Voltage Rating

Before installing SPD, verify that it has the same

voltage rating as the power distribution system.

Compare the SPD’s nameplate voltage or model

number and ensure that SPD configuration

matches the intended power source. See Table 1.

The specifier or the user of the device should be

familiar with the configuration and arrangement of

the power distribution system in which any SPD

is to be installed. The system configuration of

any power distribution system is based strictly on

how the secondary windings of the transformer

supplying the service entrance main or load are

configured. This includes whether or not the

transformer windings are referenced to earth via a

grounding conductor. The system configuration is

not based on how any specific load or equipment

is connected to a particular power distribution

system.

480V System Example: SPDs should be installed

per the electrical system, not per a load or motor’s

wiring connection. For example, a 480V three

phase motor might appear to be connected as a

480V Delta. In actuality, the serving distribution

system might be a 480Y/277V grounded Wye,

with or without a neutral pulled to the motor or

MCC. The system is still a 480Y/277V Wye,

even though the load is connected as a Delta.

A grounded Wye has a defined reference to

ground (i.e., neutral is bonded to ground).

Some Delta systems are ungrounded, which

have no reference to ground and are known to

become unstable in certain situations. Such

instability can cause line to ground voltage

fluctuations that may prematurely fail SPDs. For

this reason, the NEC

®

Article 285 has placed

SPD restrictions on ungrounded systems. As

generalizations, SPDs for ungrounded systems

can be installed on grounded systems with a

clamping performance penalty. However, SPDs

for grounded systems installed on ungrounded

systems are almost certainly destined for

premature failure. Call APT Tech Support at

(800) 237-4567 for further information.

Dry Contact Option

One set of Form C Dry Contacts are included

with the Dry Contact option. Dry Contacts change

state during inoperative conditions, including loss

of power. Any status change can be monitored

elsewhere via Dry Contacts.

Advertising