Table 1: model number decoder, Dry contacts figure 3 – Advanced Protection XDS User Manual

Page 5

Advertising
background image

A Terminal Block includes one set of Normally

Open (N.O.) and Normally Closed (N.C) contacts.

This is shown in Figure 3.

Wire Size: 30 - 12 AWG; 18 AWG Recommended.

Torque: 0.5N - m or 5lbf - in.

A typical application using a Normally Closed

configuration would connect to one set of the N.C.

and Common terminals. During an inoperative

condition, the SPDs Dry Contact would change

state from Normally Closed to Open. We generally

suggest the Normally Closed configuration

because it will detect a wiring defect, such as cut

wire(s), where N.O. will not.

Please note:

Dry Contacts are designed for low voltage or

control signals only.

Maximum switching current is 5A. Maximum

switching voltage is 240V DC or AC. Higher

energy applications require additional relay

implementation outside the SPD.

An optional Remote Monitor accessory is

available to provide visual and audible status.

The Remote Monitor will consume the set of Dry

Contacts.

Optional Flush Mount Installation

Considerations

The XD is approximately 4” deep. The unit will not

mount flush unless there is as least 4” of depth

clearance. The XD is not designed to mount flush

on a typical 2 x 4 stud wall.

Back Flange Mounting: Mount as close as

possible to protected panel. Create a wall opening

slightly larger than 6 3/4” tall x 6 1/16” wide. See

drawing. Configure a robust backing plate inside

the wall cavity 3 15/16” from the wall face such

that the SPD is supported from its back. Note the

mounting holes on the back flange. Also note that

the XD weighs 5 lbs. Be careful not to drop the

SPD into the wall.

5

Transient Eliminator

Voltage Code for Electrical System Model Family

Options

TE

02

XDS

20

4X

A

A = Audible Alarm & Dry Contacts,

Form C, 240V, 5A

R = Remote Display on 4’ cable
S = Remote Display with Surge Counter
T = Remote Display with N-G LED
U = Remote Display with N-G LED and

Surge Counter
Type 2 SPD Bearing cUL Mark

Delete Options
L = Delete L-N Protection (reduces kA rating)

G = Delete L-G Protection (reduces kA rating)

N = Delete N-G Protection (reduces kA rating)

J = Delete Noise Filter

10

=

100kA/Phase

15

=

150kA/Phase

20

=

200kA/Phase

XDS = External Mount SPD

Standard Modes

Common North American Systems:
01
= 240/120V Split Phase - 1Ø, 3W+Grnd, (Fig 1)

02 = 208Y/120V Wye - 3Ø 4W+Grnd, (Fig 2)

03 = 240/120V High Leg Delta (B High), (Fig 3)

04 = 480Y/277V Wye - 3Ø 4W+Grnd, (Fig 2)

05 = 480V Delta - 3Ø 3W+Grnd, (Fig4) & HRG Wye

08 = 600Y/347V Wye - 3Ø 4W+Grnd, (Fig2)

4X =

NEMA 4X

Non-Metallic

(size 6"x6"x4")

Enclosure Rating

Figure 1

Figure 2

Figure 3

SPLIT

2 Hots, 1 Neu, 1 Grnd

HI-LEG DELTA (B High)

3 Hots, (B HIGH),

1 Neu, 1 Grnd

WYE

3 Hots, 1 Neu, 1 Grnd

Hot (BLK)

Hot (BLK)

Neutral (WHT)

V

V

}

}

Ground (GRN)

}

Phase A (BLK)

Phase B (BLK)

Neutral (WHT)

Phase C (BLK)
Ground (GRN)

A

C

N

V

B

Phase A (BLK)

Phase B (ORNG)

Neutral (WHT)

Phase C (BLK)

Ground (GRN)

}

V

Figure 4

Figure 5

Figure 6

SINGLE POLE

1 Hot, 1 Neu, 1 Grnd

DELTA & HRG WYE

3 Hots, 1 Grnd

CORNER GROUND

DELTA (B grounded)

2 Hots, 1 Grnd

V

}

Neutral (WHT)

Hot (BLK)

Ground (GRN)

Phase A (BLK)

Phase C (BLK)

Phase B (BLK)

Ground (GRN)

}

V

Phase A (BLK)

Phase C (BLK)

Ground (GRN)

V

}

Surge Current Rating

Other Available Systems - Confirmation encouraged:

15 = 254/127V Split Phase - 1Ø 3W+Grnd (Fig 1)
18 = 480/240V Split Phase, or Two legs of Wye (Call)
21 = 220Y/127V Wye - 3Ø 4W+Grnd (Fig 2)
41 = 520Y/300V Wye - 3Ø 4W+Grnd (Fig 2)
42 = 415Y/240V Wye - 3Ø 4W+Grnd (Fig 2)
43 = 400Y/230V Wye - 3Ø 4W+Grnd (Fig 2)
44 = 440Y/250V Wye - 3Ø 4W+Grnd (Fig 2)
51 = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
06 = 240V Delta - 3Ø 3W+Grnd (Fig 4)
61 = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
07 = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2)
09 = 600V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye

(Available: 50kA, 100kA)

91 = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)

(Available: 50kA, 100kA)

11 = 120V Single Phase (Fig 5)
12 = 240V Single Phase (Fig 5) - Not split phase
13 = 127V Single Phase (Fig 5)
14 = 300V Single Phase (Fig 5)
16 = 277V Single Phase (Fig 5)
17 = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5)

TABLE 1: MODEL NUMBER DECODER

Do not create model numbers from this chart as all features are not available on all models

Remote Display

Suffix

DRY CONTACTS

Figure 3