7

Flush Mount Installation Instructions

Caution: The chassis of the XD unit can fall into

the wall cavity if the four screws attaching the

faceplate to the chassis are removed. Use caution

not to drop the unit into the wall during installation

or service.

The XD unit is approximately 4.0” deep. The unit

will not mount flush unless there is at least 3.75” of

clearance. The unit is designed to mount flush on

a typical 2 x 4 stud wall with drywall.

Depending on the depth of the wall cavity, there

are two installation procedures.

The preferred

installation utilizes Back Flange Mounting.

The back flange supports the weight of the XD

unit and service procedures are greatly simplified.

If this can not be accomplished, an alternate

Front Flange Mount is possible. Please note that

the front flange installation may create servicing

difficulties in the future.

Preferred Installation - Back Flange Mounting

Mount as close as possible to the protected panel.

Create a wall opening approximately 6 3/4” x 6

1/16”. See Figure 6. (Rotate dimensions 90° as

appropriate depending on orientation.) Configure

an appropriate backing plate inside the wall cavity

3 3/4” from the wall face such that the unit will be

supported from its back. Note the mounting holes

on the back flange attachments. Be careful not

to drop the unit into the wall. Configure electrical

conductor and conduit connection consistent with

the installation instructions on page 6. Preplan

connections such that they are completed prior

to fastening the unit to the backing plate. Install

faceplate/cover prior to energizing and testing the

unit.

Alternate Installation - Front Flange Mounting

This method is not preferred for installation as

servicing is substantially more difficult. Extra care

should be taken to NOT DROP the XD unit into the

wall. Mount as close as possible to the protected

panel. Create a wall opening approximately 6 3/4”

x 6 1/16”. See Figure 6. (Rotate dimensions 90°

as appropriate depending on orientation.) Preplan

and pre-connect electrical conductor and conduit

connections such that they are completed prior to

fastening the unit to the wall. Note that removing

the four screws attaching the front faceplate to the

unit chassis will cause the XD to fall inside the wall.

UL 1283 required language concerning the

installation of EMI Filters

a) An insulated grounding conductor that is

identical in size and insulation material and

thickness to the grounded and ungrounded

circuit supply conductors, except that it is green

with or without one or more yellow stripes, is to

be installed as part of the circuit that supplies the

filter. Reference should be made to Table 250-

122 of the National Electrical Code regarding the

appropriate size of the grounding conductor.

b) The grounding conductor mentioned in item a is

to be grounded to earth at the service equipment

or other acceptable building earth ground such as

the building frame in the case of a high-rise steel-

frame structure.

c) Any attachment-plug receptacles in the vicinity

of the filter are to be of a grounding type, and the

grounding conductors serving these receptacles

are to be connected to earth ground at the service

equipment or other acceptable building earth

ground such as the building frame in the case of a

high-rise steel-frame structure.

d) Pressure terminal or pressure splicing

connectors and soldering lugs used in the

installation of the filter shall be identified as

being suitable for the material of the conductors.

Conductors of dissimilar metals shall not be

intermixed in a terminal or splicing connector

where physical contact occurs between dissimilar

conductors unless the device is identified for the

purpose and conditions of use.

STEP 2

Insert into Wall

STEP 3

Mount the SPD

STEP 4

Mount the Lid

Figure 6

Wall Cutout

Front View

6 1/16”

Wide

6 3/4”

Tall

Supplemental Instructions for

Deep Wall Mounting (Walls over 4” thick)

Using the Enclosed Mounting Feet

STEP 1

Prepare Wall and SPD

FLUSH MOUNT “/FM” (PREFERRED INSTALLATION)

Advertising