Page 13

Advertising
background image

13

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

MODUCONTROL

CONTROL PANEL

compatibility EMC 89/336/EEC and 92/31/EEC.

Door-lock isolating switch

THE electric control board can be accessed by

isolating the main power supply via the door

interlock. This lever can be locked using one or

more padlocks during maintenance interventions

to prevent the machine being powered up

accidentally. (Lock off procedure)

Control board

Allows complete control of the unit.

For a more in-depth description please refer to

the user manual.

− compressors magnet circuit-breaker protection.

− fans magnet-circuit breakers protection;

− auxiliary magnet circuit-breaker protection

− Heat exchanger inlet/Water outlet temperature

probes

− Gas temperature probe one on the for pressing

line and coil

− External air temperature probe WITH DCPX

ACCESSORY

2.4.

ELECTRONIC MODU CONTROL

ADJUSTMENT

MODU_CONTROL

Temperature control of the outlet water with

proportional-integral algorithm: maintains

average outlet temperature at value set

Self-adapting differential switch:

guarantees minimum functioning times of the

compressor in systems with low water content.

Intelligent defrosting for pressure reduction:

allows to determine when the coil is effectively

defrosted, avoiding excessive defrost operation

Hot gas injection defrosting: In this way the

machine consumes less energy, increases

heating capacity, keeps efficiency high and

prevents temperature drops at the terminals

(very important in plants with low water content

Emergency defrosting by cooling cycle reversing:

to overcome more serious conditions

Set-point compensation with external

temperature (with external air probe accessory):

reduces energy consumption

Condensation check based on the pressure

rather than on temperature for absolute stability

(with DCPX revs. adjuster accessory)

Inverse condensation check for the heat pump

functioning mode also in summer (withDCPX

revs. adjuster accessory).

Pre-alarms with automatic reset: in the case of alarm,

a certain number of re-starts are allowed before

latching out.

Alarm on the∆T: to identify wiring errors (reverse

rotation) or blocked cycle reversing valve.

Compressor functioning hours count

Compressor peak count.

Historical alarms

Autostart after voltage drop.

Local or remote control

Display of unit status:

a.

Voltage presence

b.

Compressor ON/OFF

c.

Functioning mode (hot/cold)

d.

Alarm active

Probes, transducers and parameters display

a.

Water outlet

b.

Water inlet

c.

Coil temperature (heat pumps)

d.

Pressing line gas temperature

e.

External air temperature (heat pumps,

cooling only with DCPX and probe)

f.

Flow pressure (heat pumps)

g.

Intake pressure (heat pumps)

h.

Temperature error (sum of the

proportional and integral error)

i.

Stand-by times for start-up/switch-off of

the compressor

Alarms management

a.

Low pressure

b.

High pressure (primary alarm: the

pressure switch directly blocks power supply to

compressor)

c.

High discharge temperature

d. Anti-freeze

e.

Water differential flow meter/pressure

switch

f.

Alarm on the ∆T

Alarms with automatic reset with limited number of re-

starts before blockin ON/OFF from external contact

Change season from external contact

For further information please refer to user

manual