14. SOUND DATA

Sound power

Airedale determines sound power values

in agreement with the 9614 Standard,

in compliance with that requested by

Eurovent certification.

Sound Pressure

Sound pressure measured in free

field conditions with reflective surface

(directivity factor Q=2) at 10mt distance

from external surface of unit, in

compliance with ISO 3744 regulations.

DURING COOLING MODE

DURING HEA

TING MODE

Total sound levels

Octave band [Hz]

Pow.

dB(A)

Pressure.

125

250

500

1000

2000

4000

8000

dB(A)

10 m

dB(A)

1 m

Sound power for centre of band [dB] frequency

020

61.0

30.0

43.0

70.0

64.1

59.1

52.7

46.7

41.0

35.7

025

61.0

30.0

43.0

70.0

64.1

59.1

52.7

46.7

41.0

35.7

030

68.0

37.0

50.0

75.4

69.6

64.0

63.5

56.7

51.2

44.6

040

68.0

37.0

50.0

75.4

69.6

64.0

63.5

56.7

51.2

44.6

050

69.0

38.0

51.0

76.5

69.2

64.8

64.6

58.9

53.7

46.1

070

69.0

38.0

51.0

76.5

69.2

64.8

64.6

58.9

53.7

46.1

080

69.0

38.0

51.0

73.8

69.4

65.8

64.1

59.5

56.5

51.0

090

68.0

37.0

50.0

74.0

68.5

64.5

62.2

59.3

56.4

48.1

100

76.0

44.0

58.0

61.2

66.0

71.4

72.0

68.9

60.5

48.6

150

77.0

45.0

59.0

62.4

67.3

72.2

72.7

69.7

61.5

49.6

200

78.0

46.0

60.0

63.6

68.4

73.4

73.5

70.5

62.5

50.6

KEY

- Water input temperature

12 °C

- Water Temperature °C

7 °C

- External air temperature

35 °C

15. PARAMETER

CALIBRATION OF SAFETY

AND CONTROL

CONTROL PARAMETERS

ECL

min

standard

max

Cooling set point

°C

-6

7

18

Heating set point

°C

35

48

55

Defrosting mode

°C

-9

3

4

Total differential

°C

3

5

10

Autostart

auto

020°

025°

030°

040°

050°

070°

080°

090°

100°

150°

200°

SAFETY AND CONTROL COMPONENTS ELECTRIC DATA

Fan magnet circuit breakers MTV1

A

2

2

2

2

2

2

2

2

2

2

2

Fan magnet circuit breakers MTV2

A

-

-

-

-

2

2

2

2

2

2

2

Compressors magnet circuit breakers MTC1

230V A

16

16

20

25

18

21

25

25

-

-

-

Compressors magnet circuit breakers MTC1

400V A

2.2

2.2

6

8

10

13

15

16

10/10

12.5/12.5

15/15

High pressure pressure switch

bar

42

42

42

42

42

42

42

42

42

42

42

Low pressure pressure switch

cold

bar

2

2

2

2

2

2

2

2

2

2

2

Low pressure transducer

cold

bar

4

4

4

4

4

4

4

4

4

4

4

High pressure transducer

bar

40

40

40

40

40

40

40

40

40

40

40

020H 025H 030H 040H 050H 070H 080H 090H 100H 150H 200H

SAFETY AND CONTROL COMPONENTS ELECTRIC DATA

Fan magnet circuit breakers MTV1

A

2

2

2

2

2

2

2

2

2

2

2

Fan magnet circuit breakers MTV2

A

-

-

-

-

2

2

2

2

2

2

2

Compressors magnet circuit breakers MTC1/2

230V-1 A

16

16

20

25

-

-

-

-

-

-

-

400V-3 A

2.2

2.2

6

8

10

13

15

16

10/10

12.5/12.5

15/15

High pressure pressure switch

bar

42

42

42

42

42

42

42

42

42

42

42

Low pressure pressure switch

cold

bar

2

2

2

2

2

2

2

2

2

2

2

Low pressure transducer

cold

bar

4

4

4

4

4

4

4

4

4

4

4

PdC

bar

2

2

2

2

2

2

2

2

2

2

2

High pressure transducer

bar

40

40

40

40

40

40

40

40

40

40

40