Ecochill chiller, Environmental considerations – Airedale EcoChill 6kW - 46kW User Manual

Page 5

Advertising
background image

5

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

Environmental Considerations

Freeze Protection

Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes the

units subject to low ambient temperatures.

Units with supply water temperatures below +5°C

Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be exposed to

freezing temperatures.

Units subject to ambient temperatures lower than 0°C

Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that the con-

centration is capable of protection at least 3°C lower than ambient.

Water / glycol solution is constantly circulated through all waterside pipework and coils to avoid static water from freezing.

Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the solution

freeze point

(1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).

(1) Referrer to your glycol supplier for details

Environmental Policy

It is our policy to:

Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.

Train personnel in sound environmental practices.

Pursue opportunities to conserve resources, prevent pollution and eliminate waste.

Manufacture products in a responsible manner with minimum impact on the environment.

Reduce our use of chemicals and minimise their release to the environment.

Measure, control and verify environmental performance through internal and external audits.

Continually improve our environmental performance.

CE Directive

Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:

Electromagnetic Compatibility Directive (EMC)

2004/108/EC

Low

Voltage

Directive

(LVD)

2006/95/EC

Machinery

Directive

(MD)

89/392/EEC

version

2006/42/EC

Pressure Equipment Directive (PED)

97/23/EC

To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the

Declaration of Conformity, supplied with each product.

Advertising