Ecochill chiller, Cooling line version c motorcondensing – Airedale EcoChill 6kW - 46kW User Manual

Page 34

Advertising
background image

34

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

COOLING LINES

Model

Line length [m]

Gas line Ø [mm]

Liquid line Ø [mm]

R410A [g/m]

ECL 020 C

0-10

12.7

9.52

70

10-20

12.7

9.52

70

20-30

12.7

9.52

70

ECL 025 C

0-10

12.7

9.52

70

10-20

12.7

9.52

70

20-30

12.7

9.52

70

ECL 030 C

0-10

12.7

12.7

120

10-20

12.7

12.7

120

20-30

15.88

12.7

130

ECL 040 C

0-10

12.7

12.7

120

10-20

15.88

12.7

130

20-30

15.88

12.7

130

ECL 050 C

0-10

15.88

15.88

190

10-20

15.88

15.88

190

20-30

18

15.88

190

ECL 070 C

0-10

15.88

15.88

190

10-20

18

15.88

190

20-30

18

15.88

190

ECL 080 C

0-10

15.88

15.88

190

10-20

18

15.88

190

20-30

22

15.88

210

ECL 090 C

0-10

18

15.88

190

10-20

22

15.88

210

20-30

22

15.88

210

ECL 100 C

0-10

28.00

15.88

230

10-20

28.00

15.88

230

20-30

28.00

15.88

230

ECL 150 C

0-10

28.00

15.88

230

10-20

28.00

15.88

230

20-30

28.00

15.88

230

ECL 200 C

0-10

35.00

15.88

260

10-20

35.00

18.00

310

20-30

35.00

18.00

310

13. COOLING LINE VERSION C

MOTORCONDENSING

If evaporator is placed lower than con-

denser, risers are needed in the riser,

to favour the transporting of oil towards

the compressor. By line length, dis-

tance measured between the units on

the liquid line, is intended. For addition-

al information please contact company.

Advertising