Ecochill chiller, Dcpx, Operational limits – Airedale EcoChill 6kW - 46kW User Manual

Page 19

Advertising
background image

19

EcoChill

Chiller

Technical Manual 7300221 V1.1.0_02/2013

5.1.

COOLING MODE FUNCTIONING

5.2.

COOLING MODE FUNCTIONING

FOR MOTOR CONDENSING C

VERSIONS

5.3.

HEATING MODE FUNCTIONING

FOR HEAT PUMPS

-6

-10

-5

-15

0

5

10

15

20

25

30

35

40

46

50

-4

15 16 17 18

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

-2

46

46

40

Temperature of the water produced °C

External air temperature °C

-10

-10

-15

-5

0

5

10

15

20

25

30

35

40

46

50

-4

-6

-8

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

-2

46

46

40

DCPX

External air temperature °C

External air temperature °C

DCPX

-5

-10

20

25

30

35

40

45

50

40

35

30

25

20

15

10

5

0

50

50

Temperature of the water produced °C

d.b. external air temperature °C

5.4. PROJECT DATA

High

pressure

side

Low

pressure

side

Acceptable maximum pressure

bar

42

25

Acceptable maximum temperature

°C

120

52

Acceptable minimum temperature

°C

-10

-16

CONTACT

AIREDALE

Functioning with

glycoled water

STANDARD

functioning

Functioning with gly-

coled water and DCPX

Functioning with DCPX

Vers. Z

Vers. Y

6.

OPERATIONAL LIMITS

The units, in standard configuration, are not suitable for instal-

lation in salty environments. The maximum and minimum limits

for water flow rate to the heat exchanger are indicated by the

pressure drop diagram curves.

For functioning limits, please refer to the diagrams below, valid

for ∆t = 5 °C.

ATTENTION:

Use of produced water with a temperature lower than

4 °C is only allowed by specific envisioned versions.

(Versions Z-Y).

If the machine is to be operated out of the limits indicated in the

diagram, please contact Airedale technical support dept.

If it is installed in a particularly windy zone, a windbreak should

be provided to avoid unstable operation of the DCPX device.