Installation & Maintenance : 6259675 IM V1.4.0 10/2013

Chill

ers

ULT

IM
A CO

M

PACT

Installation Data

ANTI VIBRATION MOUNTING – OPTIONAL

COMPONENTS:


1

Locating Screw

2

Retaining Nut & Washer

3

Levelling Screw

4

Levelling Lock Nut

5

Retaining Studs

6a

Upper Retaining Nuts

6b

Lower Retaining Nuts

7

Spring assembly

8

Pressure Plate

9

Top Plate

10

Bolting-down holes

2

1

6a

5

6b

10

9

8
7

3

4

DIMENSIONS:

B

A

C

D

E

F

E

A

(1)

B

C

D

E

UCC30-70

2

S

P

R

IN

G

136

110

180

148

16

11

UCC75, 80, 100, 125 & 150
UCCU30-70
UCCU75, 80, 100, 125 & 150
UCFC75-150
UCC110, 130, 160-450

4

S

P

R

IN

G

180

130

225

186

20

16

UCCU110, 130, 160-450
UCFC160-450
UFC200-750
URAC75-450
USC200-750
UWC75-450

(1)

Unloaded dimension

(2)

Refer to relevant Loose Parts Instructions sheet for positioning of each mount.

INSTALLATION

1

Locate and secure mount using bolting down holes (10) in base plate.

2

Ensure mounts are located in line with the unit base.

3

If applicable, remove compressor enclosure covers to allow access to mount fixing holes in
the unit base.

4

Lock the upper retaining nuts (6a) to the underside of the top plate (9) before a load is
applied.

5

Remove retaining nut and washer (2), lower the unit onto the mounts and replace retaining
nut and washer.

6

Beginning with the mount with the largest deflection, adjust the height of each mount using
the levelling screw (3).

CAUTION

Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a time as
this may overload and damage springs.

7

When all mounts are level, lock each into place using the levelling lock nut (4).

8

Lock all retaining nuts (6a and 6b) to the extreme ends of the retaining studs (5).

CAUTION

Do not connect any services until all anti vibration mounts have been fully adjusted.