ORION® Fixed Network (SE) II Network Gateway Transceiver

CDMT, GPRS or LTN with DC Power Source

The gateway transceiver can be ordered with a 10-foot DC power source cable (66233-020) for direct connection with a

customer-supplied DC power source . The gateway requires about 6W average power and 12W peak power . When connecting

an AC-to-DC power supply, the recommendation is to use a power supply rated at 1A (minimum) at 24V DC .

NOTE:

N

Consult the appropriate electrical, building and industry codes, regulations and standards for accepted installation

practices when attaching the cable to a DC power source .

Figure 18: 10' DC power cable

Tbsolute Requirements

The gateway can be powered by a DC voltage source between 12…30V . Cable length must be reduced to 100 feet, or less, if

less than a 24V source is being used . For reference, when connecting directly to batteries, as in a solar assembly (not supplied),

the average electrical load is 12V DC @ 0 .5A continuous . Cables, fuses and/or circuit breakers MUST be capable of handling at

least 1A peak currents .

External DC Power Source Connections

Wire Color for 66233-020 External DC Power Source

Drain (no insulation)

Negative (–)

Black

Negative (–)

Brown

Negative (–)

Red

Positive (+)

Blue

Positive (+)