6.4 Mode 2 - 4-20 mA input -

In this mode, the on-time of the cycle will

automatically adjust to match the received mA input value. When the mA
input value is equal the programmed maximum, the pump will run
continuously.
Four values must be programmed:
1) ON-T = The amount of time the pump will run, per cycle, when the

minimum mA value is received. (Typically programmed to zero)

2) mA minimum = The mA input value that will result in the on time (ON-

T). (Typically programmed to 4 mA)

3) TOT-T = The total cycle time.
4) mA maximum = The mA input value that will result in the pump running

continuously.

Example:
ON-T setting = 0 seconds
mA minimum setting = 4mA
TOT-T setting = 8 seconds
mA maximum setting = 14.8mA

6

4

8 10 12 14 16 18 20

0

2

4

6

8

Pump Run-T

ime (Sec.)

Milliamp input (mA)

A-100NE

Page 14

+ Set the pump for mode 2. Press the

MODE button until MODE 2 is shown on
the LCD display.

+ Enter the programming mode. At the

same time, press the RUN/STANDBY
button and the MODE button. A blinking
ARROW will point to the word
PROGRAM indicating the program mode
has been activated. The on time ON-T

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

2

00.0

MODE

ON-T

SEC

icon will blink. The currently selected time unit icon will be displayed.
The current on time setting will be displayed and the left most (selected)
digit will blink. The decimal is fixed and cannot be moved.

+ Pressing the DIGIT button will increase the selected digit.
+ Pressing the FIELD button will select a new the digit to the right or the

time unit.

+ Press the DIGIT button to increase the selected digit or time unit.

A-100NE

Page 15

+ Press the MODE button to exit the on time

programming screen and enter the mA
minimum programming screen. The mA
icon will blink. A blinking ARROW will
appear next to the word MINIMUM. The
current minimum mA setting will be
displayed and the left most (selected) digit

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

2

04.0

mA

MODE

will blink.

+ Pressing the DIGIT button will increase the selected digit.

total time TOT-T icon will blink. The currently selected time unit icon will
be displayed. The current total time setting will be displayed and the left
most (selected) digit will blink. The decimal is fixed and cannot be
moved.

+ Pressing the DIGIT button will increase the selected digit.
+ Pressing the FIELD button will select a new the digit to the right or the

+ Pressing the FIELD button will select a

new the digit to the right.

+ Press the DIGIT button to increase the

selected digit.

+ Press the MODE button to exit the mA

minimum programming screen and enter
the total time programming screen. The

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

2

00.0

MODE

SEC

TOT-T

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

2

20.0

mA

MODE

time unit.

+ Press the DIGIT button to increase the

selected digit.

+ At the same time, press the RUN/STANDBY button and the MODE

button. A blinking ARROW will point to the word RUN indicating the run
mode has been activated.

NOTE: If while in the program mode no buttons are pressed within 60
seconds, the circuitry will automatically return to the run mode.