Time specified period hold with trigger, Peak, valley, peak-to-peak and mean value) – FUTEK IPM600 (D610) Digital Display User Manual

Page 78

Advertising
background image

7.HOLD FUNCTIONS

67

7-6-4. Time Specified Period Hold with Trigger

(Peak, Valley, Peak-to-Peak and Mean Value)

Hold is detected during the predetermined time (hold detection time) from the point in

time when the indicated value crosses the auto start level. The hold is released by turning

on the T/H signal as a reset signal.

The H/E output signal is on between the instant when the hold detection time ends and

the instant when the T/H signal is turned on.

(Example) Time Specified Period Peak Hold with Trigger

t1 A delay time between the instant when the indicated value exceeds the auto start

level and the instant when the value to be held is detected
0.5ms (max.)

t2 A delay time between the instant when the hold detection time is expired and the

instant when the value to be held is determined
1.0ms (max.)

t3

A minimum reset signal width required for releasing the hold

1.0ms (min.)

Indicated Value

t3

Sensor Input Value

Detection

t

HOLD

HI-LO Limit
Judging Output

H/E

Hold Period

t2

t1

Decide

T/H

Time

Auto Start Level

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

HOLD

PEAK

ON

Blink

ON

OFF

ON

OFF

OFF

OFF

HOLD

Button