MAXIM Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 3 – Electrical Installation

3-3.1.2 Universal Inputs

The MAXIM I, II, III, and 1010 controllers are equipped with Universal Inputs that can be configured to

suit a wide range of applications as described in Table 3-3 below. Each Universal Input has a signal

terminal (+) and a reference terminal (–).

Table 3-3: 

Input/Output Range for Universal Inputs

Input Type

Input Range

Output Range

Analogue

0-10VDC

0-10VDC

Thermistor

High Thermistor 100kΩ – 680kΩ

-20°C to 100°C

Low Thermistor 662kΩ – 12kΩ

-50°C to 20°C

Lux Sensor

1MΩ – 0Ω

3 to 2500 LUX

Digital

Voltage

0 – 10VDC

OFF or ON

Contact

Open or Closed

OFF or ON

Pulse Counter

Voltage

0 – 10V Square Wave
20ms Min. ON Time
20ms Min. OFF Time

0 to 25 pulses per second

Contact

Open or Closed
20ms Min. ON Time
20ms Min. OFF Time

0 to 25 pulses per second

Duty Cycle

Voltage

0 – 1 Square Wave
1 – 13Hz

0 to 100%

Contact

Open or Closed
1 – 13Hz

0 to 100%

Please note that the LUX Sensor input mode is suitable for switching based on ambient light levels, but is NOT

suitable for any operation which requires the accurate measurement or recording of light levels.

NOTE