Minimax power source specifications, 3.2 minimax controllers (mm01 / mm02) – Innotech Maxim User Manual

Page 32

Advertising
background image

MAXIM Installation Instructions

Page 32

© Mass Electronics Pty Ltd 2011

Edition 2.0 dated 20/11/2013

3-3.2 MiniMAX Controllers (MM01 / MM02)

This section of the manual provides wiring information for the MiniMAX MM01 and MM02 controllers.

Information is provided on wiring a power source and all associated inputs and outputs.

The general layout of the input and output terminals for each of these controllers is illustrated in

Figure 3-7 below.

3-3.2.1 Power Input

The MiniMAX controllers are powered by a 24VAC power source. The operating voltage must meet the

requirements of Safety Extra Low Voltage (SELV) to EN60730. The transformer used must be a Class 2

safety transformer in compliance with EN60742 and be designed for 100% duty. It must also be sized

and fused in compliance with local safety regulations. Power input specifications for the MiniMAX
controllers are detailed in Table 3-5 below.

Figure 3-7:  MiniMAX (MM01 & MM02) Controller Terminal Connection Layout

Table 3-5: 

MiniMAX Power Source Specifications

Power Source

Rating

24VAC ±10%, 50/60 Hz, Nominal Transformer rating with maximum TRIAC load:

35VA

24VAC ±10%, 50/60 Hz, Nominal Transformer rating with no TRIAC load:

10VA

Advertising