MAXIM Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 3 – Electrical Installation

3-3.3.3 TRIAC Outputs

The VAVMax and MicroMAX controllers are equipped with four TRIAC outputs used for switching the

24VAC power supply through to the outputs of the controller. There are four 24V terminals for each

TRIAC output, and two 0V terminals that are shared by the four TRIAC outputs. The TRIAC outputs

are rated at a minimum current of 20mA, and maximum current of 250mA. The TRIAC outputs can

operate in two modes: Pulse Width Modulation (PWM) or Digital (ON/OFF). The output range for both

modes of operation are described in Table 3-12 below.

3-3.3.4 Fixed Thermistor Input

The VAVMax and MicroMAX controllers are equipped with a fixed thermistor input labelled TEMP. The

fixed thermistor input has a signal terminal (+) and a reference terminal (–). This input is designed

for use with the Innotech SEN Series Detectors. The sensing range and accuracy for the SEN Series

Detectors is as follows:

• Nominal sensing range -5°C to 60°C

• Accuracy +/-3.5%FS (R25°C = 10kΩ)

Table 3-12: 

VAVMax and MicroMAX Controllers: Modes of Operation for TRIAC Outputs

TRIAC Output Mode

Output Range

Digital

ON or OFF

PWM Output

0-100% (0-10VDC)

The use of pilot relays is recommended when switching high voltage and inductive loads.

NOTE