3-3.2.3 TRIAC Outputs

The MiniMAX controllers are equipped with four TRIAC outputs used for switching the 24VAC power

supply through to the outputs of the controller. There are four 24V terminals for each TRIAC output,

and two 0V terminals that are shared by the four TRIAC outputs. The TRIAC outputs are rated at

a minimum current of 20 m A and maximum current of 250 m A. The TRIAC outputs can operate in

two modes: Pulse Width Modulation (PWM) or Digital (ON/OFF). The output range for both modes of

operation are described in Table 3-8 below.

3-3.3 VAVMax and MicroMAX Controllers

This section of the manual provides wiring information for the VAVMax and MicroMAX controllers.

Information is provided on wiring a power source and all associated inputs and outputs.

The general layout of the input and output terminals for each of these controllers is illustrated in

Figure 3-8 below.

Table 3-8: 

MiniMAX Controllers: Modes of Operation for TRIAC Outputs

TRIAC Output Mode

Output Range

Digital

ON or OFF

PWM Output

0-100% (0-10VDC)

Figure 3-8:  VAVMax and MicroMAX Controller Terminal Connection Layout

Advertising