MAXIM Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 5 – Commissioning

5-2.2.5 TRIAC Outputs

The following items should be checked and verified for proper operation of the TRIAC Outputs on

applicable controllers:

• Verify correct polarity of the wiring connected to the TRIAC outputs.
• Inspect the controlling device for any defects or problems.
• Verify that the current draw for any contactors are within the tolerance of the TRIAC outputs.
• Power ON the TRIAC output (force ON using MAXMon).
• Check the TRIAC output voltages and verify proper operation of the controlling device

V

AC

V

DC

+

CHECKING ANALOGUE

OUTPUT RESISTANCE

Connected to equipment

or device

2000

Figure 5-5:  Checking Analogue Output Resistance

A TRIAC output cannot be tested without a load applied. Therefore a load of a minimum current rating of 20mA

must be applied for correct operation of the TRIAC outputs.

CAUTION