Minimax controller power input terminals, Minimax universal inputs/outputs – Innotech Maxim User Manual

Page 33

Advertising
background image

Page 33

MAXIM Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 3 – Electrical Installation

3-3.2.2 Universal Inputs / Outputs

The MiniMAX controllers are equipped with seven Universal Inputs/Outputs which can be configured

with MAXCon software to be used as inputs or outputs. Each Universal Input/Output has a signal

terminal (+) and a reference terminal (–). The types of inputs and outputs that can be configured and

the respective range for each are shown in Table 3-7 below.

When a UIO on a MiniMAX controller is configured as a Thermistor input type, it is designed to be used

with Innotech SEN Series Detectors. The sensing range and accuracy for the SEN Series Detectors is

as follows:

• Nominal sensing range: -5°C to 60°C

• Accuracy +/-3.5%FS (R25°C = 10kΩ)

A single transformer may be used to supply voltage to more than one controller, but you must ensure

that the planned load is well within the rating of the transformer. The transformer output terminal

designated as AC Neutral must be solidly earthed to the main earth link of the enclosure panel. The

dedicated power input terminals are Terminals 1 and 2 and are detailed in Table 3-6 below.

Table 3-6: 

MiniMAX Controller Power Input Terminals

Terminal

AC Supply

1

24VAC

2

0VAC (Neutral

Table 3-7: 

MiniMAX Universal Inputs/Outputs

UIO Type

Input Range

Output Range

Analogue Input

0 – 10VDC

0 – 10VDC

Dry Digital Input

Open or Closed

OFF or ON

Voltage Digital Input

0 – 10VDC

OFF or ON

Thermistor Input

96kΩ – 677Ω

-20°C to 100°C

LUX Sensor Input

20kΩ – 400Ω
3 to 1000 LUX

0 to 2500 LUX

Dry Pulse Counter Input

0 – 10V Square Wave
1 to 13Hz

0 to 25 pulses per second
±1 pulse accuracy

Voltage Pulse Counter Input

0 – 10V Square Wave
20ms Min. ON Time
20ms Min. OFF Time

0 to 25 pulses per second
±1 pulse accuracy

Analogue Output

0 to 100%

0 – 10VDC

Digital Output

OFF or ON

0 or 10VDC

PWM Output

0 to 100%

0 to 100% Duty Cycle at 13Hz

It is not recommended to use the Pulse Counter on these controllers for accumulation as these controllers are not

equipped with battery backup or flash RAM. The MAXIM II, MAXIM III, and MAXIM 1010 controllers are better suited

for such situations.

NOTE

Advertising