System Installation and Startup

Technical Data

Maximum Pressure

10 bar

140 psi

Minimum Pressure

2.8 bar

38 psi

Backwash Flow Rate per unit 8 m

3

/hr 35

gpm

Maximum Temperature

70

°C 158°F

pH 4-11

4-11


2” Spin Klin Battery

Installation

A. Make sure that the inlet and outlet orientation is correct (shown by arrows on filter).

B. Prior to start-up check for any transport damage to the unit (system operates under pressure!).

C. Connect backwash drainage line.

D. Cover clamps need to be properly closed.

Start-up Operation

Start the backwash cycle, making sure that all system components function correctly.

Filter Load-up during Start-up

Close the downstream (flow control) valve (if available).

Flush few cycles until clean.

Slowly reopen the downstream valve.

If the pressure difference remains high, check and see if the flow rate is too high.

An excessive flow rate through the filter causes excessive pressure loss.