Spin Klin – System Maintenance



Monthly Maintenance

Check inlet /outlet pressures:

In case the pressure differential is above 5 m / 7

PSI

.

Activate automatic backwash of the Spin Klin filter battery.

In the event that the pressure differential remains high check for possible failures.

Check for leakages from the drain manifold:

In case there is a leakage of water during the filtration stage, check for possible failure at the

backwash valve seals.

Backwash controller performance:

Check that the controller timing parameters are correctly adjusted and activate automatic

backwash cycle. In the event of possible failure at the backwash controller, check for

possible failures.

Cleaning of the Command Filter:

Close the command filter inlet valve, release the pressure trapped at the command filter,

remove the cover. Thoroughly clean the filtration element and then reinstall the command

filter element and cover, then open the inlet valve.

Winterization:

In order to prevent the filter battery becoming damaged during water freezing - drain all the

water from the filter battery and the command filter and leave the drain valve open.