ROTRONIC CF8-W-Disp-CO User Manual

Page 11

Advertising
background image

Dokument
UMA 147

Rev
1

Page
11 (16)


4.

Push ENTR(+-) once. The display shows EC and two digits. Enter the access

code to the service menu. If the default code is used do like this: Push
MENU(+) until the digits stop. The display shows EC55. If the correct code is
not entered before the time limit exceeds the sensor returns to DEFAULT.


5.

Push ENTR(+-) once. The display shows SPCO to set the carbon monoxide
set point.

6.

Push ENTR(+-) once. The display shows the carbon monoxide set point e.g.
ex 35 ppm. Push MENU(+) to increase the set point value in steps of 1 ppm.

Push ESC(-) to decrease the set point value in steps of 1 ppm.


7.

Push ENTR(+-) once when the set point is set. The display shows SPCO.

Push ESC(-) to return to DEFAULT.


8.

Push MENU(+) once to reach the carbon dioxide set point.

The display shows SP C.


9.

Push ENTR(+-) once. The display shows the carbon dioxide set point e.g. 750
ppm. Push MENU(+) to increase the set point value in steps of 50 ppm.

Push ESC(-) to decrease the set point value in steps of 50 ppm.


10.

Push ENTR(+-) once when the set point is set. The display shows SP C.

Push ESC(-) to return to DEFAULT.


11.

Push MENU(+) once to reach the setting of analogue outputs.

The display shows AOUt.


12.

Push ENTR(+-) to reach the output to be set. The display shows An and two
digits e.g. An 01. Step to the requested output by pushing MENU(+).


13.

Push ENTR(+-) to reach the setting of the MIN value. The display shows Set
L.

14.

Push ENTR(+-) to set the MIN value of the output. The display shows the
numerical value in % e.g. the standard setting 0.0 % or previously set value.
Push MENU(+) to increase the MIN value. Push ESC(-) to decrease the MIN
value. Push ENTR(+-). The display shows Sure. Push ENTR(+-) to save the
setting and return to Set L. Push MENU(+) or ESC(-) to return to Set L without
saving the new setting.

15.

Push MENU(+) to reach the setting of the MAX value. The display shows Set
H.

16.

Push ENTR(+-) to set the MAX value of the output. The display shows the
numerical value in % e.g. the standard setting 100.0 % or previously set value.
Push MENU(+) to increase the MAX value. Push ESC(-) to decrease the MAX
value. Push ENTR(+-). The display shows Sure. Push ENTR(+-) to save the

Advertising