Maintenance – ROTRONIC CF8-W-Disp-CO User Manual

Page 15

Advertising
background image

Dokument
UMA 147

Rev
1

Page
15 (16)

6

64

Memory Error
Non-fatal error during memory
operations.

Check detailed settings and
configuration with UIP software version
4.3 and higher.

7

128

Warm Up state
Is always set after power up or
power failure. Resets after restart
sequence

If it doesn’t disappear in half a minute,
check power stability.


Table V. Error codes

Note 1
. Any probe is out of range. Occurs, for instance, during over exposure of CO

2

sensor, in which case the error code will automatically reset when the measurement values
return to normal. Could also indicate the need of zero point calibration. A background
calibration using push button function ”bCAL” will cure this error (a more exact zero
calibration using ”CAL” may be performed later, if required). If the CO

2

readings are normal,

and still the error code remains, the temperature or relative humidity sensor can be defect or
the connections to these are broken.

Please remark: If several errors are detected at the same time the different error code numbers
will be added together into one single error code!

Maintenance


The CF8-W-Disp-CO is basically maintenance free. An internal self-adjusting
calibration function takes care of normal long term drift associated to the CO and CO

2

sensor. To secure the highest accuracy, a time interval of five years is recommended
between calibrations, unless some special situations have occurred. A zero
calibration can be performed by use of the push button functions, or for a complete
overview by use of a PC together with the UIP software version 4.3 (or higher). This
software can be free downloaded from

www.rotronic.com

. A RS232-cable is needed

and can be ordered from Rotronic. The cable is to be connected to the UART port
slide connector (Fig 10). For change of control parameters and re-calibration (CO

2

and CO) this PC tool has to be used. The check can be done on site without
interfering with the ventilation system.