Output Configurations


A label on the inner side of the sensor lid shows the configuration of the outputs at
the time of product delivery. The sensors/controllers are supplied from the factory
(unless otherwise ordered) with 0...10VDC linear outputs for Out(1) and Out(2).
Out(4) is an open collector output (see Table II). If different output configurations are
needed for the application, these have to be reconfigured before the unit is powered
up. Default values are 0-10 V.







Figure 5 The connection terminal area of the CF8-W-Disp-CO with jumpers and terminals. The

terminal DI1 may be used for forced ventilation. If the sensor has a heater it is connected to

and

.

DI1

~

+

~

+

DI1 Switch
for alarm
test

Jumpers to
choose
between
voltage or
current

outputs

Jumper to choose
between open
collector or 0-10V
linear signal

Jumper to
choose
communication
protocol

Jumper for
configuring the
linear output
start point to 0%
or 20%

start

point