Dipswitch settings for vent length, Installation installation manual – Takagi T-H3M-IN/OS User Manual

Page 12

Advertising
background image

12

Page

Installation

Installation Manual

-DIPswitch settings for Vent length-

Vent length

Two-pipe and Single pipe

5 to 50 ft.

(DEFAULT)

No 6 : ON

No 7 : OFF

51 to 100 ft.

No 6 : OFF

No 7 : OFF

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

Vent length

Two-pipe

5 to 20 ft.

(DEFAULT)

No 6 : ON

No 7 : OFF

21 to 40 ft.

No 6 : OFF

No 7 : OFF

41 to 70 ft.

No 6 : ON

No 7 : ON

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

Set DIPswitches shown in the tables below depending on the vent length Only adjust switches with a black
square Black squares indicate the position of the switch

Vent length

Single pipe

5 to 45 ft.

(DEFAULT)

No 6 : ON

No 7 : OFF

46 to 70 ft.

No 6 : OFF

No 7 : OFF

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

Vent length

Single pipe

5 to 6.5 ft.

No 6 : ON

No 7 : ON

OFF

ON 1 2 3 4 5 6 7 8 9 10

2 inch venting

3 inch venting

4 inch venting