Installation, General – Takagi T-H3M-IN/OS User Manual

Page 7

Advertising
background image

7

Page

Installation Manual

INSTALLATION

GENERAL

1. Follow all local codes, or in the absence of local codes, follow the most recent edition of the National

Fuel Gas Code: ANSI Z2231/NFPA 54 in the USA or CAN/CSA B1491 Natural Gas, Propane Installation

Code in Canada

2. All gas water heaters require careful and correct installation to ensure safe and efficient operation

This manual must be followed exactly Read the “Safety Guidelines” section

3. The manifold gas pressure is preset at the factory It is computer controlled and should not need

adjustment

4. Maintain proper space for servicing Install the water heater so that it can be connected or removed

easily Refer to the "Clearances" section on p 9 for proper clearances

5. The water heater must be installed in a location where the proper amount of combustible air will be

available to it at all times without obstructions

6. The electrical connection requires a means of disconnection, to terminate power to the water heater

for servicing and safety purposes

7. Do not install the water heater where the exhaust vent is pointing into any opening in a building or

where the noise may disturb your neighbors Make sure the vent termination meets the required

distance by local code from any doorway or opening to prevent exhaust from entering a building (refer

to p 17 to 19)

8. Particles from flour, aerosols, clothes dryers and other airborne contaminants may clog the air vent,

build up and reduce the functions of the rotating fan, cause improper burning of the gas, or cause

damage to the water heater Regularly ensure that the area around the water heater is dust- or debris-

free Regular maintenance is recommended for these types of environments Sealed combustion is

recommended too

9. The 140 Indoor (T-H3M-DV) model is to be installed indoors only The model is equipped with a

thermistor and hi-limit switch for the exhaust gas, detecting excess temperatures within the flue and

enabling the water heater to safely stop operation if needed These components are always monitoring

exhaust gas conditions in order to prevent heat damage to ABS, PVC, CPVC, or Polypropylene (Plastic)

venting if ABS, PVC, CPVC, or Polypropylene is used If the exhaust gas temperature exceeds 140 °F

(60 °C) these components will enable the water heater to safely stop operation (These components

are not installed on the outdoor model since the exhaust vent is built-in)

• The Indoor model requires 3 inch, or 4 inch diameter intake air supply pipe The intake pipe must

be sealed airtight

• Air supply pipe can be made of aluminum flexible tube, ABS, PVC, CPVC, Polypropylene,

corrugated stainless steel, or Category lll / IV stainless steel Regarding exhaust pipe, please refer

to p11 for detailed information

• Sidewall venting is recommended for the Indoor model Vertical venting (roof termination) is

acceptable

• The manufacturer recommends running the exhaust vent and the intake pipe as parallel as possible

10. The 140 Outdoor (T-H3M-OS) model is only to be installed outdoors and only in the area with mild,

temperate climates

The Outdoor model shall be wall-mounted or mounted on a stand Locate the Outdoor model in an

open, unroofed area and maintain the minimum clearances (Refer to p9)

Installation