TOHO ELECTRONICS TTM200 User Manual

Page 24

Advertising
background image

24

6.8 Composition of an ASCII request message (transmitted from a high-level

computer to this product)

 For the codes a) through g), see "6.10 Description of ASCII codes."

6.8.1 Composition of a read request message

a) Start code

“:”

b) Slave address

“0” , “1”

c) Function code

“0” , “3”

d) Register address

High level

“0” , “0”

First register address

Low level

“0” , “0”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

f)

LRC

“F” , “A”

g) End code

CR, LF


6.8.2 Composition of a write request message

a) Start code

“:”

b) Slave address

“0” , “1”

c) Function code

“1” , “0”

d) Register address

High level

“0” , “1”

First register address

Low level

“0” , “0”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

h) Number of byte items

“0” , “4”

Register

2

i)

First register data
(a low-level word)

High level

“0” , “0”

Data composition is ①, ②, ③,
and ④H. (① represents 1
byte.)

Low level

“0” , “0”

First register data
(a high-level word)

High level

“0” , “0”

Low level

“0” , “0”

f)

LRC

“E” , “8”

g) End code

CR, LF


6.8.3 Composition of a store request message

a) Start code

“:”

b) Slave address

“0” , “1”

c) Function code

“1” , “0”

d) Register address

High level

“2” , “0”

First register address

Low level

“0” , “E”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

h) Number of byte items

“0” , “4”

Register

2

i)

First register data
(a low-level word)

High level

“0” , “0”

The data about the storage of settings
is arbitrary.

Low level

“0” , “0”

First register data
(a high-level word)

High level

“0” , “0”

Low level

“0” , “0”

f)

LRC

“B” , “B”

g) End code

CR, LF

Advertising