10 description of ascii codes – TOHO ELECTRONICS TTM200 User Manual

Page 25

Advertising
background image

25

6.9 Composition of ASCII response messages (transmitted from this product

to a high-level computer)

 For the codes a) through g), see "6.10 Description of ASCII codes."

6.9.1 Response message for a read request message

a) Start code

“:”

b) Slave address

“1” , “1”

c) Function code

“0” , “3”

h) Number of byte items

“0” , “4”

Register

2

i)

First register data
(a low-level word)

High level

“0” , “0”

Data composition is ①, ②, ③,
and ④H. (① represents 1
byte.)

Low level

“0” , “0”

First register data
(a high-level word)

High level

“0” , “0”

Low level

“0” , “0”

f)

LRC

“5” , “3”

g) End code

CR, LF


6.9.2 Response message for a write/store request message

a) Start code

“:”

b) Slave address

“0” , “1”

c) Function code

“1” , “0”

d) Register address

High level

“0” , “1”

First register address

Low level

“0” , “0”

e) Number of registers

High level

“0” , “0”

Fixed at 2

Low level

“0” , “2”

f)

LRC

“E” , “C”

g) End code

CR, LF


6.9.3 Response message in the case of an error

a) Start code

“:”

b) Slave address

“0” , “1”

h) Function code

“8” , “3”

In the case of an error, the function

code for the request message +
80H is entered.

j)

Error code

“0” , “3”

f)

LRC

“7” , “9”

g) End code

CR, LF


Advertising