40 control setting mode (set4) – TOHO ELECTRONICS TTM200 User Manual

Page 40

Advertising
background image

40

Control setting mode (set4)

toho

modbus

Screen

character

Name

Command Remark

Identifier

Absolute

(DEC)

Relative (hex)

BNK

41025

0400

bANK Switch to another bank

RWLB

BKH

41139

0472

bANKH Bank upper limit setting

RWLB

Pay attention to MODBUS
address.

SV1

41027

0402

SV Control set

RWLB

SLH

41029

0404

SLH SV limiter upper limit

RWLB

SLL

41031

0406

SLL SV limiter lower limit

RWLB

□MD

41033

0408

Md Control mode

RWLB

00000:RUN
00001:MAN
00002:RdY
00003:TIME1
00004:TIME2
00005:TIME3

CNT

41035

040A

CNt Set a control type

RWLB

TYP

41037

040C

tYP Set a PID control type

RWLB

BMD

41039

040E

bMd Set type B mode

RWLB

DIR

41041

0410

dIR Set a forward/backward action

RWLB

MV1

41043

0412

MV1 Main control operation amount

RWLB

M1G

41045

0414

MV1G Set an output gain

RWLB

TUN

41047

0416

tUN Set a tuning type

RWLB

ATG

41049

0418

AtG Set an AT factor

RWLB

ATC

41051

041A

AtC Set an AT sensitivity

RWLB

□AT

41053

041C

At Start/stop tuning

RWLB

00000: Stop
00001: Start

□P1

41055

041E

P1 Set a main control proportional band

RWLB

□I1

41057

0420

I Set an integration time

RWLB

□D1

41059

0422

d Set a derivative time

RWLB

□T1

41061

0424

t1 Set a main control proportional period

RWLB

ARW

41063

0426

ARW Anti-reset windup

RWLB

MH1

41065

0428

MLH1

Main control operation amount limiter, upper
limit

RWLB

ML1

41067

042A

MLL1

Main control operation amount limiter, lower
limit

RWLB

OU1

41069

042C

oU1 Set a main control change limiter rise

RWLB

OD1

41071

042E

od1 Set a main control change limiter decline

RWLB

SFM

41119

045E

SFM Set a main control soft-start output

RWLB

Pay attention to MODBUS
address.

SFT

41121

0460

SFt Set a main control soft-start time

RWLB

Pay attention to MODBUS
address.

FA1

41073

0430

FAL1 Set a main control anomaly

RWLB

1TS

41127

0466

tS1

Set a main control loop anomaly PV
threshold

RWLB

Pay attention to MODBUS
address.

1MS

41129

0468

MS1

Set a main control loop anomaly MV
threshold

RWLB

Pay attention to MODBUS
address.

1PS

41131

046A

PS1

Set a main control loop anomaly PV change
threshold

RWLB

Pay attention to MODBUS
address.

LP1

41075

0432

LoP1 Set a main control loop anomaly time

RWLB

CMD

41077

0434

CMod Set an OFF point position selection

RWLB

□C1

41079

0436

C1 Set a main control sensitivity

RWLB

CP1

41081

0438

CP1 Set an OFF point position

RWLB

FD1

41123

0462

Fdt1 Main control protection off timer

RWLB

Pay attention to MODBUS
address.

ND1

41141

0474

Ndt1 Main control protection on timer

RWLB

Pay attention to MODBUS
address.

MV2

41083

043A

MV2 Auxiliary control operation amount

RWLB

M2G

41085

043C

MV2G Set an auxiliary control output gain

RWLB

□P2

41087

043E

P2 Set an auxiliary control proportional band

RWLB

□T2

41089

0440

t2 Set an auxiliary control proportional period

RWLB

MH2

41091

0442

MLH2

Auxiliary control operation amount limiter,
upper limit

RWLB

ML2

41093

0444

MLL2

Auxiliary control operation amount limiter,
lower limit

RWLB

OU2

41095

0446

oU2 Set an auxiliary control change limiter rise

RWLB

OD2

41097

0448

od2

Set an auxiliary control change limiter
decline

RWLB