Switching on the ups battery circuit breaker, Connecting devices to the ups – HP Parallel Uninterruptible Power System User Manual

Page 24

Advertising
background image

UPS installation 24

Switching on the UPS battery circuit breaker

When the UPS is plugged in and the battery circuit breaker is on, the UPS automatically enters Standby mode

and begins charging the batteries.

Connecting devices to the UPS

CAUTION:

Do not plug laser printers into the UPS output receptacles. The instantaneous current

drawn by this type of printer can overload the UPS.

Before connecting devices, verify that the UPS will not overload by checking that the ratings of the devices do

not exceed the UPS capacity. If the equipment rating is listed in amps, multiply the number of amps by the

nominal AC source to determine the VA.
To provide additional receptacles:

For the 8kVA models—Plug a PDU into the UPS output receptacle at the end of the power cord.

For the 12kVA models—

a.

Install the included output module on the rear rack frame.

Advertising