HP Parallel Uninterruptible Power System User Manual

Page 69

Advertising
background image

UPS operations 69

Description

Available settings

Default setting

Relay Config

Relay: [Alarm-1][X-Slot 1-1/2/3/4] or

[X-Slot 2-1/2/3/4]

Alarm 1: empty

X-Slots (1 or 2)

Setup: [On Battery][Summary Alarm][On
Bypass][UPS OK][custom][empty]

#1: UPS OK
#2: On Bypass

#3: Summary Alarm

#4: On Battery

Signal Inputs

[empty][Logic]

For more information, see "Programmable

signal inputs (on page

77

)."

<empty>

Serial Port Config

Port: [X-Slot-1][X-Slot 2/Serv]

Speed: [19200][9600][2400][1200]

19200

Parallel Operation Settings (only
available in parallel configuration)

Parallel Operation Mode: [Redundant
Mode][Capacity Mode]

This setting is not available for six-unit

systems (Redundant Mode only)

Redundant Mode

Parallel XCP: [System][Sub Unit]

Select System for HP communication
applications. Select Sub Unit for other

applications.

System

Auto ID Restart: [Done][Restart]

Select Restart to reinitialize
auto-identification. For more information,

see "Auto-identification (on page

78

)."

None

Battery Setup

Number of ERMs: [0 through 4]

For more information, see "Configuring the

UPS (on page

67

)."

0

(internal batteries only)

Battery Low Alarm Level:

[1.750 through 1.950 volts per cell]

1.880 V/cell

Automatic Battery Tests:
[Enabled][Disabled]

Enabled automatically runs the battery test

once a month.

Enabled

Power Strategy

[High Efficiency][Standard]

For more information, see "Normal mode
(on page

65

)."

High Efficiency

Start Screen

HP logo
Mimic screen (on page

64

)

HP logo

User Password

[Enabled][Disabled]

If enabled is selected, the password is

USER.

Disabled

Audible Alarms

[Normal Sound][Disabled]

Normal Sound

Unsynchronized Transfer to

Bypass

[Allowed][Not Allowed]

Not Allowed

Transfer to Bypass When
Overload

[After a delay][Immediately]

After a delay

Automatic Start Delay

-1 through 32767 seconds

(-1 means disabled)

0s

Control Commands from X-Slot 1 [Allowed][Not Allowed]

Allowed

Control Commands from X-Slot
2/Serv

[Allowed][Not Allowed]

Allowed

X-Slot Signal Input Activation

0 through 65 seconds

5s