HP Parallel Uninterruptible Power System User Manual

Page 85

Advertising
background image

Maintenance 85

o

Set the card for the middle UPS(s) to Pins 2 and 3.

4.

Install the Parallel UPS Card into an open X-Slot on the rear of the UPS.

5.

Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled.
The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on
the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on

page

78

)" .

6.

Verify that all the terminal blocks and jumpers are installed in each UPS.

7.

Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting

the card OUT port on one UPS to the card IN port on the next UPS.

Advertising