Configuring the parallel ups card – HP Parallel Uninterruptible Power System User Manual

Page 41

Advertising
background image

UPS installation 41

Configuring the Parallel UPS Card

1.

Unpack the Parallel UPS Card, and be sure that the card was not damaged during shipment.

NOTE:

If installing another X-Slot card, be sure to install the Parallel UPS Card in X-Slot

Communication Bay 2.

2.

Remove the UPS X-Slot communication bay cover, and retain the screws.

3.

Set the jumper pins on the Parallel UPS Card according to the parallel configuration.
For three or more paralleled UPSs:

o

Set the cards of the first and last UPS to Pins 1 and 2.

o

Set the card for the middle UPS(s) to Pins 2 and 3.

4.

Install the Parallel UPS Card into an open X-Slot on the rear of the UPS.

5.

Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled.
The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on

the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on
page

78

)" .

6.

Verify that all the terminal blocks and jumpers are installed in each UPS.

7.

Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting
the card OUT port on one UPS to the card IN port on the next UPS.