Normal mode, Standard mode, Full-time standard mode – HP Parallel Uninterruptible Power System User Manual

Page 65: High efficiency mode, Continuous double-conversion mode

Advertising
background image

UPS operations 65

o

Standalone UPS configuration—See "Powering down the standalone UPS (on page

72

)."

o

Individual UPS in a parallel configuration—See "Powering down an individual paralleled UPS (on
page

72

)."

o

Parallel UPS configuration—See "Powering down the parallel system (on page

73

)."

2.

Power to the load ceases.

IMPORTANT:

While in Standby mode, the UPS maintains the charge on the batteries, but no

power is available at the output receptacles. The UPS remains in Standby mode until an alternate
mode is selected or until utility power is removed.

Normal mode

In Normal mode:

Power is available at the UPS receptacles.

The UPS charges the batteries as necessary.

Depending on input power conditions, the UPS automatically changes modes. The UPS has three types of

Normal mode:

Standard mode (on page

65

)

Full-Time Standard mode (on page

65

)

High Efficiency mode (on page

65

)

Standard mode

If the input line exceeds normal operating range, the UPS transfers to Standard mode (Online mode) to
produce a regulated output voltage. When the input line returns to normal operating range, the UPS returns

to High Efficiency mode (on page

65

).

Full-Time Standard mode

Full-Time Standard mode (continuous Online mode) is user selectable for full-time operation.

High Efficiency mode

By default, the UPS operates in a High Efficiency mode that minimizes heat contribution to the rack

environment. The system bypass input directly supplies the system output with three-phase AC power, and the
UPS automatically transfers to double-conversion (Normal mode (on page

65

)) operation as needed. The

battery recharges as necessary.

Continuous double-conversion mode

Continuous double-conversion mode is available only for loads less than 10 kW (86%). If the load exceeds

the 10 kW limit while in Standard mode, the UPS switches to High Efficiency mode until the load is reduced

below 9 kW. After three attempts within one hour to operate in Standard mode, the UPS locks into High
Efficiency mode for one hour to prevent continuous cycling.