Wiring guidelines, Using the axlink connector for data and power – AMX VTM-D15/A User Manual

Page 23

Advertising
background image

Installation and Wiring

19

VTM-D15/A 15" MultiMedia Touch Panel Systems

3.

Tighten the screws to secure the wire in the connector. Do not tighten the screws excessively;

doing so may strip the threads and damage the connector.

Wiring guidelines

The AXB-TPI/3 requires 12 VDC power to operate properly. Each module adds 500 mA of current

consumption (in addition to the baseline 630 mA for a stand-alone unit) on the TPI/3 system. The

unit should only have one source of incoming power.

Using the AXlink connector for data and power

To use the AXlink 4-pin connector for data communication with the Central Controller and power

transfer from the PSN6.5 power supply, the incoming PWR and GND cable from the PSN6.5 must

be connected to the AXlink cable connector going to the Central Controller. FIG. 18 shows the

AXlink wiring diagram. Always use a local power supply to power the TPI/3 unit.

Wiring Guidelines - No Module

Wiring Guidelines - One Module

Wire size

Maximum wiring length

Wire size

Maximum wiring length

18 AWG

186.30 feet (56.78 meters)

18 AWG

103.87 feet (31.66 meters)

20 AWG

117.87 feet (35.93 meters)

20 AWG

65.72 feet (20.03 meters)

22 AWG

73.49 feet (22.40 meters)

22 AWG

40.97 feet (12.49 meters)

24 AWG

46.32 feet (14.12 meters)

24 AWG

25.83 feet (7.87 meters)

Wiring Guidelines - Two Modules

Wiring Guidelines - Three Modules

Wire size

Maximum wiring length

Wire size

Maximum wiring length

18 AWG

72.01 feet (21.95 meters)

18 AWG

55.10 feet (16.79 meters)

20 AWG

45.56 feet (13.89 meters)

20 AWG

34.86 feet (10.63 meters)

22 AWG

28.40 feet (8.66 meters)

22 AWG

21.74 feet (6.63 meters)

24 AWG

17.90 feet (5.46 meters)

24 AWG

13.70 feet (4.18 meters)

Using more than one source of power to the AXB-TPI/3 can result in damage to the
internal components and a possible burn out.

FIG. 18 AXlink connector wiring diagram

PWR (+)

GND (-)

Local +12 VDC power supply
(coming from the PSN power supply)

PWR +

AXP/TX

AXM/RX

GND -

PWR +

AXP/TX

AXM/RX

GND -

To the Central Controller

To the AXB-TPI/3

Do not connect the wire from the PWR terminal on the Central Controller to the PWR
terminal on the TPI/3 unit when you connect an external power supply. Make sure to
connect only the AXM, AXP, and GND wires on the TPI/3’s AXlink connector when
using the PSN6.5 power supply.

Advertising