Temperatures menu – State SSE-120 User Manual

Page 20

Advertising
background image

20

teMperatures Menu

operating set point

User adjustable setting 90°F to 190°F range; factory default is

120°F. When the water temperature sensed by the control system

from the immersion Temperature Probe reaches the Operating Set

Point the control system will end the heating cycle. A call for heat

will be activated again when the water temperature drops below the

Operating Set Point minus the 1st Differential Setting.

Example: Operating Set Point is 120°F, the 1st Differential Setting is

2°F (factory default). A call for heat will be activated when the sensed

water temperature drops to 118°F.

differential settings

Adjustable user setting(s) 1°F to 20° range; factory default is 2°F.

The water heaters covered in this manual will have between 1

and 5 heating elements. There is at least one Differential Setting

on all models. There will be additional Differential Settings for each

additional heating element installed.

operating sequence
On a water heater equipped with 3 heating elements, with an

Operating Set Point of 120°F and all Differential settings at 2°F the

On/Off sequencing of heating elements would be as follows:

table 8.

ELEMENT

NUMBER

DIFFERENTIAL

SETTING

TURN ON TEMP

TURN OFF TEMP

Element 1

2°F

118°F

120°F

Element 2

2°F

116°F

118°F

Element 3

2°F

114°F

116°F

tank temperature

Non adjustable information display. Current water temperature

as sensed by the control system from the immersion Temperature

Probe.

tank probe offset

User adjustable setting -5°F to +5°F range; factory default is 0°F.

If the current Tank Temperature is sensed (from the immersion

Temperature Probe) at 120°F and the offset is adjusted to -5°F the

control system would calibrate or “offset” the Tank Temperature to

115°F. Heating cycles would then start/stop based on the calibrated

Tank Temperature.

Used to calibrate for slight differences in control system temperature

sensing. This can improve the precision of temperature control in

the storage tank and at points of use. This feature can also be used

to compensate for building recirculation loops (hot water returning

to the storage tank) that may cause the heating cycle to terminate

prematurely.