3. Characteristics of water supply.

Regardless of water treatment, the elements should be

examined regularly.

Lime scale accumulations may cause noises to occur during

operation.

It is recommended that a heating element be removed periodically

for examination. If it is scaled, all of the elements should be removed

and cleaned. If the tank bottom has an accumulation of sediment it

should be cleaned.

Lime scale should be removed by dissolving the accumulation in

UN-LIME

®

delimer. Do not use muriatic or hydrochloric acid base

deliming solutions to remove lime scale from the elements.

THE PROCESS FOR LIME SCALE REMOVAL IS AS FOLLOWS:

1. Turn off electrical disconnect switch.

2. Drain the heater following DRAINING instructions.

3. Open front panel.

4. Disconnect the element wiring. Try not to disturb the wiring

unnecessarily and reconnection will be easier.

5. Unscrew each element.

6. Remove the elements and gaskets from the openings.

Use a twisting, pulling action to remove elements scaled

beyond the size of the tank openings.

Brush loose scale from elements.

7. Lime scale removal:

Place limed ends of heating elements into UN-LIME delimer

and allow scale to dissolve. Do not permit delimer or water

to contact heating element electrical terminals.

Silicates, sulfates, and aluminates must be removed

by scraping or other mechanical means. Lime scale

dissolvents will not remove these types of scale which are

occasionally encountered.

8. Flush cleaned ends of elements with water when deliming or

cleaning is completed.

Call the toll free phone number on the back cover of this Instruction

Manual to purchase UN-LIME and heating element gaskets.

OTHER SCALE REMOVAL:

1. Remove sediment and scale from the tank bottom through

the access provided by the element openings or drain valve

opening.

The cold water inlet valve and drain valve may be opened

to aid the cleanout process.

2. Clean remaining gasket material from tank and element flanges.

Don not reuse original element gaskets.

3. Put new gaskets on each element and install into tank openings.

Uniformly tighten element bolts. Torque to approximately

32 ft/lbs.

4. Attach element wires to connection points from which they were

removed.

5. Follow FILLING instructions to restore hot water service.

Check for water leaks around elements and proper

operation when heater is filled.

Close the panel.