alarM output setup Menu

Permits user to set the condition (from a list of options) for when

the CCB’s integral alarm output relay will be energized. Alarm relay

connections (common, normally open, normally closed) are located on

the J3 terminal strip on the CCB - see wiring diagrams. Alarm output

relay contacts are capable of switching

1 amp maximum at 120 Vac.

The alarm relay operates in the background according to the settings

in this menu and is not capable of disabling water heater operation.

The alarm relay is used for external notification/verification of

various operational conditions such as fault conditions and heating

mode status. This relay can be used with building EMS (Energy

Management System) and other external supervisory controls.

output function

Adjustable user setting. Available options for the Alarm Output

Function setting are:

Heating Mode: Used for heating mode on/off status notification.

Enable / Disable Closed: Used for notification and/or verification of

the enable/disable circuits open/closed status. There are two enable/

disable circuits available for external supervisory control(s) at the J7

socket on the CCB - see wiring diagrams. Enable/disable circuit(s)

status can be viewed in the Heater Status Menu.

Temp < Heater SP: Used for external notification when current tank

temperature drops below Operating Set Point.

Temp < Alarm SP: Used for external notification when current tank

temperature drops below programmable Alarm SP.

Fault or Alert: Used for external notification whenever a Fault or

Alert condition is active.

Fault: Used for notification whenever a Fault condition is active.

Disabled: Disables the Alarm Relay Output Function.

alarm sp

Adjustable user setting (90°F to 190°F) the control system uses for

the “Temp < Alarm SP” function described above. This setting has no

effect with any other Alarm Output functions.

alarm output settings

Changing the user settings in this menu is done using the same

methods for changing the Operating Set Point.

Service Note: Adjustable user settings in the Alarm Output Setup

menu are unaffected by Restore Factory Defaults.

dIsplay settInGs Menu

Permits user to set display options for viewing information on the

UIM’s LCD screen.

temperature units

Adjustable user setting that changes temperature units display to

Celsius °C or Fahrenheit °F.

backlight delay

Adjustable user setting that determines how long the UIM’s LCD

backlight remains illuminated after a key has been pressed. Available

settings are; Always Off, 10, 30 or 60 seconds and Always On.

contrast

Adjustable user setting to adjust the UIM’s LCD screen contrast

between text and background.

display settings

Changing the user settings in this menu is done using the same

methods for changing the Operating Set Point.

Service Note: Adjustable user settings in the Display Settings menu

are unaffected by Restore Factory Defaults.

heater InforMatIon Menu

This menu displays non adjustable operational information.