Configuring Loggers

38

©

2011 Vaisala Canada Inc

To change the sample interval on the currently-connected log-
ger:
1

Select

Logger | Sample Timing

.

2

Under

Sample Interval

, use the drop-down lists to set the

Days

,

Hours

,

Minutes

, and

Seconds

to the desired sample

interval. If you want to use a sample interval of once per
minute, click

Default

. You can choose intervals ranging

from a minimum of ten seconds to once every 24 hours
(with the exception of the VL-1000-VLT, VL-1200 and
models SP-1016, SP-1200, SP-1416, VL-1016, VL-1416,
which have minimum sample intervals of one minute).
The total period covered by a logger before the memory
is full depends on how many channels are enabled and
the sample interval setting. This information is
automatically calculated in the

Log Time

section of the

Logger Sample Timing window.

Note:

Running the logger with a sample interval
shorter than one minute for a prolonged time
shortens the battery life.