3-7-5. Set the power switch to the ON position. Check the meters and

indicators on the front panel of the inverter. The voltage bar graph

should indicate 11 to 14 volts (22 to 28V when 24V version is used)

depending on the voltage of the power source. If does not, check

your power source and the connections to inverter.

The other indicators should be off.

3-7-6. Set power inverter switch to the OFF position, the indicator lights may

blink and the internal alarm may sound momentarily.

This is normal. Plug the test load into the AC receptacle on the front

panel of the inverter. Leave the test load switch off.

3-7-7. Set power inverter switch to the ON position and turn the test load On.

The inverter should supply power to the load.

If you plan to accurately measure the true output r.m.s. voltage of

inverter, a meter such as FLUKE 45 BECKMAN 4410 or TRIPLETT

200 must be used.

WARNING!

You may observe a spark when you make this

connection since current may flow to charge

capacitors in the power inverter.

Do not make this connection in the presence of

flammable fumes Explosion or fire may result.