CS420-L and CS425-L Pressure Transducers

'Switch to next transducer, delay 10000 use before measurement
BrFull6W(WellDepth(LoopCount),1,mv5000,mV50,1,Vx1,
1,5000,True

,True,0,250,Mult(LoopCount),Offset(LoopCount))

LoopCount = LoopCount + 1

NextSubScan

PortSet (1 ,0)' Deactivate AM16/32


CallTable

WellData

NextScan
EndProg

8.1.3.3 CR5000 Program

'CR5000
'For use with an AM16/32 in a 6 wire configuration, with four sensors.

Public WellDepth(4)

Dim LoopCount
Dim Mult(4)
Dim Offset(4)

DataTable (WellData,1,-1)
DataInterval

(0,30,Sec,10)

Sample

(4,WellDepth(),FP2)

Maximum

(4,WellDepth(),FP2,False,True)

Minimum

(4,WellDepth(),FP2,False,True)

EndTable

BeginProg
Scan

(5,Sec,0,0)


'Load multiplier and offset for each individual sensor

Mult(1)

=

2.2975

Mult(2)

=

1.0560

Mult(3)

=

3.0001

Mult(4)

=

1.9821


Offset(1)

=

.36781

Offset(2)

=

.4011

Offset(3)

=

.2103

Offset(4)

=

1.0029


PortSet (1 ,1 )

'Activate AM16/32

LoopCount = 1

'Reset loop counter

SubScan

(0,Sec,4)

PortSet

(2

,1

)

'Turn Control Port 2 on

Delay

(0,10,mSec)'Wait

10msec

PortSet(2,0)

'Turn Control Port 2 off -- this sequence

'provides a short 5V pulse that advances the

'mux

to

the

next

relay

BrFull6W(WellDepth(LoopCount),1,mV5000,mV50,1,Vx1,1,
5000,True,True,0,250,Mult(LoopCount),Offset(LoopCount))