2 program type composite, Program type - composite -24, 2 program type - composite – Campbell Scientific PVS4100/4120/4150 Portable Automatic Samplers User Manual

Page 64

Advertising
background image

Section 5. Programming

5-24

This option will cause the sampler to step to
a new container regardless of the status of
the SAMPLE INITIATION setting. For
example, the actual sampling may be under
the control of a flowmeter and taking
samples based on the flow rate as
determined by pulses or 4-20mA input to the
controller. When the user-programmed
timed interval has elapsed, the controller
will step to a new container. The Timed
Step
can be set for any interval up to 99
hours 59 minutes. Progress of the step timer
can be viewed by selecting View, Program
Type
and pressing ENTER twice. Thus you
may view the step timing and the amount of
time until the next step occurs.

5.5.2 PROGRAM TYPE - Composite

The following sequence of entries are made
on the Touchpad to describe how the
Sampler controller is to store the samples it
takes, in the hardware specified in its
configuration. The ACTIVE SETTINGS are
not being altered.

1. Press the SET key.

2. Press the PROGRAM TYPE key.

3. Press an ARROW key. Continue until
Composite is shown on the display (for
storage in single container).

4. Press the ENTER key.

Advertising