7 D Version – Buffered direct connect keypad scanning

The ProxPro reader is available with a 3 x 4 matrix keypad. The keypad is independent of the ProxPro
reader and only provides a voltage output from the keypad. This mode requires a separate cable to be
supplied that connects to the Keypad wiring to the host. This method of interfacing the keypad requires
additional processing by the host. This includes toggling the select low line to ground to enable the
keypad, debouncing of the keys, decoding of the keypad voltages, timing between key entries, as well
as others depending on the host.

This table indicates the voltage on the keypad wires when a key is pressed. This is available on the
Buffered Direct Connect ProxPro 5355XXDXX versions.

Table 1 Buffered Direct Connect KeyPad Data

Wire Colors

Key #

Gray

Violet

Red /
Yellow

Pink

Tan

White /
Blue

White /
Green

1 LO HI HI HI LO HI HI

2 LO HI HI HI HI LO HI

3 LO HI HI HI HI HI LO

4 HI LO HI HI LO HI HI

5 HI LO HI HI HI LO HI

6 HI LO HI HI HI HI LO

7 HI HI LO HI LO HI HI

8 HI HI LO HI HI LO HI

9 HI HI LO HI HI HI LO

* HI HI HI LO LO HI HI

0 HI HI HI LO HI LO HI

# HI HI HI LO HI HI LO

HI represents a voltage of +5 volts in reference to the ProxPro ground.

LO represents the ProxPro ground.

Notes:

1. The system is to be used on a single point ground system.

2. On the Buffered Direct Connect toggle Select Low (White/Yellow) wire to ground to enable the above

keypad outputs.