Customer settings menu: “settings – American Standard TRACER CH532 User Manual

Page 12

Advertising
background image

12

CG-SVU01B-E4

Customer settings menu:
“Settings”

From the menu screen, select

Settings” then press

.

Following screen will appear:

Enter password:”0000” (factory-set)

Press

and cursor will move to

first field of password. Pressing

or

will change the value from 0

to 9999. Keeping pressure on

or

will move the numbers fast.

Press

to confirm password.

Pressing will

allow

navigation from screen 1 to 5 as
shown hereafter:

1. Setpoints

To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Cooling Stp = Cold water setpoint
(-12 to 20°C - factory setting: 7°C)
Heating Stp = Hot water setpoint
(20 to 60°C - factory setting: 45°C)
Aux Wat Stp = Auxiliary setpoint
(-12 to 60°C - factory setting: 10°C)
Aux Wat = Auxiliary setpoint from
external source:
Enable = Auxiliary setpoint validated
Disable = Auxiliary setpoint non-
validated

. Automatic cooling and heating
mode setpoints reset

TRACER CH532 offers the possibility
to offset cold and/or hot water
setpoints according to ambient air
temperature.
The automatic setpoint reset
program will allow you to change
the water temperature setpoint
(cooling and heating mode) with the
ambient temperature. This function
can be used in conjunction with the
external setpoint reset function.

Figure 4

1. Leaving water temperature setpoint
2. Starting point
3. Ending point
4. Reset delta
5. Active set point

Below the reset starting point, the
water temperature setpoint will be
the normal setting. Between the
starting and ending point the
setpoint will vary proportionally with
the ambient temperature. After the
ending point, the setpoint will stay
at its maximum or minimum value.

2.1 Cooling mode setpoint reset
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Cold Water Reset: Ambient
temperature based cold water
setpoint offset

Y = Enabled
N = Disabled (factory setting)

Start Point: Starting point (-15 to 50°C
- factory setting: 20°C)
End Point: Ending point (-15 to 60°C
- factory setting: 30°C)
Reset Delta: Reset amplitude (-15 to
15°C - factory setting: 10°C)

3. Heating mode setpoint reset
(Reversible chillers only)
To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Hot Water Reset: Ambient
temperature based hot water
setpoint offset

Y = Enabled
N = Disabled (Factory setting)

Start Point: Starting point
(-15 to 50°C - factory setting: 20°C)
End Point: Ending point
(-15 to 60°C - factory setting: 30°C)
Reset Delta: Reset amplitude
(-15 to 15°C - factory setting: 10°C)

User password

0000

Cooling Stp

07.0°C

Heating Stp

45.0°C

Aux Wat Stp

10.0°C

Aux Wat

Disable

5

1

4

2

3

Cold water reset

N

Start Point

20.0°C

End Point

30.0°C

Reset Delta

10.0°C

Hot water reset

N

Start Point

20.0°C

End Point

30.0°C

Reset Delta

10.0°C

Ambient

temperature

Cooling StP

07.0°C

Heating StP

45.0°C

Aux Wat StP

10.0°C

Aux Wat

Disable