Customer settings menu: “settings – American Standard TRACER CH532 User Manual

Page 13

Advertising
background image

Comp seq: Compressor sequencing

The Auto sequence intend to have
equivalent numbers of starts and
stops and an equivalent number of
compressor working hours. The
compressor start order will prioritize
the compressors which have the
least number of working hours.
Ckt1/2: Circuit 1/2 operation

Enable: circuit operational
Disable: circuit non-
operational

Note: It is possible to disable both
circuit 1 and 2. Water pump will be
kept in operation

5. Customer Inputs and Outputs

To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Analog Input: Signal type

0..10V (factory setting)
0..1V
0..20mA
4..20mA

Note: the total amplitude
corresponds to reset delta of +20°C
between 0%(0V,OA or 4 mA) and
100% (10V,1V, or 20 mA)

Ana. Input External setpoint reset

Y = Enabled
N = Disabled

Pump Timer: Time between unit stop
(by keyboard or external contact)
and stop of the pump
(1 to 10 min - factory setting = 1 min)

6. Customer outputs configuration

Default I/O: (NO9 / NO11)
This output will be used to give an
information about the circuit status:
A configuration parameter will allow
to choose between the following
three indications concerning this
circuit:

ALL: All alarms (manual and
automatic reset)
ALL But LA: All alarms but
without Low Ambient alarm
MR only: Manual reset
alarms only (factory setting)

Status output: (NO10)

Add Heat: indicate an
additionnal heat demand
Unit State Send data telling
that at least one
compressor is ON
(factory setting)

CG-SVU01B-E4

13

4. Operating mode

To access one of the parameters

displayed, press

and change

value using

or

. Confirm the

value by pressing

Mode: Operating mode

Cooling: Cold water
production (default factory
setting)
Heating: Hot water
production (Reversible
chillers only)
Extern: (external control)

Note: When switching from cooling
to heating mode or from heating to
cooling mode, unit will stop for 15 s
before restarting.
To allow chiller waterflow rate
adjustment disable circuit 1 and 2,
then start the unit.

1-2: fix order

Single circuit

Dual circuit

Start order

A1,B1

A1, A2, B1, B2

Stop order

B1, A1

B2, B1, A2, A1

2-1: fix order

Single circuit

Dual circuit

Start order

B1,A1

A2, A1, B2, B1

Stop order

A1, B1

B1, B2, A1, A2

Rotation

Single circuit

Dual circuit

Start order

A1,B1

A1, A2, B1, B2

Stop order

A1,B1

A1, A2, B1, B2

Auto (default factory setting)

Mode

Cooling

Comp seq

Auto

Ckt1

Enable

Ckt2

Enable

Analog Input

0..10V

Ana. Input

Disable

Customer settings menu:
“Settings”

Alarm Out:

MR only

State Out:

Unit state

Pump Timer:

01 min